Directional time graded protection for parallel feeders
~ Two parallel feeders are often used for the reliability of the power supply.
~ so that in case of a fault on one feeder , a certain amount of power flow is turned on by the other feeder and complete shutdown dose not occur.
~ non-directional over current relay can not be used for protection of this parallel feeder as it dose not contain discrimination.
~ below this understood from the example shown. figure
~ parallel feeders ab and cd suppose A,B,C coke has a non-directional relay
~ And the operating time of the relay near D is 0.5 second and the operating time of the bag near A and C is 1.0 seconds.
~ suppose the feeder has a fault above f.
~ fault current will be fed via CP and ABDF.
~ the relay near both have low time setting.
~ hence the relay on B and D will operates first.
~ the wife relay will then operate.
~ now this fault belong to the feeder on the CD so the single CD feeder is also isolated from B
~ to overcome this problem a non-directional relay with inverse time characteristic is placed on the generator side of the feeder and a revers power types relay with instantaneous time characteristic is placed on the load side.
~ now suppose F is a fault on the feeder CD. the fault will feed in two ways..
~ the first CPR route and the second ABDI route.
~ The power flow of section AB is in the right directional ( dose not revers).
~ there for the relay on B cannot be operated.
~ when the directional of power is reversed in section DF. relay characteristic is kind of instantaneous.
~ so the relay on D will operated immediately and trip the circuit breaker.
~ this will stop feeding the fault ABDF route.
~ so the flow flowing the fault ABDF route.
~ therefor the relay on a will not operated.
~ the fault is still fed by C so the relay on C will trip.
~ this the faulty feeder CD will be isolated and the healthy feeder will be in the circuit protection of ring mains

0 Comments