plug setting multiplier
~ the ratio of fault current and pickup current of the relay coil is called plug setting multiplier
~ plug setting multiplier = fault current of relay coil/pickup current = fault current of relay coil/rated current of CT secondary * current setting
~ suppose plug setting 150% so
~ratio of CT 500/5 and
~ fault current 3750 A
~fault current of relay 5*3750/500 = 37.5
~A and the pickup current 150*5/100=7.5 and
~ plug setting multiplier = 37.5/7.5=5
time setting multiplier
~ the relay also has a time setting similar to the current setting.
~ the time at which the relay operates can be adjusted.
~ given the time setting multiplier for this.
~ this dial is calibrated from 0 to 1 in step 0.05 suppose the time derived from the time PSM curve is 4 second and the time setting multiplier is sets to 0.2 the operating time of the relay is 4*0.2=0.8 second
~ rotating the time setting knob change the distance between fixed contact and moving contact.